Omnigrad T TST602
RTD thermometer, surface measurement

Omnigrad T TST602
RTD thermometer, surface measurement ©Endress+Hauser

Suitable for the temperature measurement of pipe surfaces or container walls

Simple, fast and retrofit installation directly on the pipe or container wall, independent from the process connection, leads to a wide choice of applications: Verifying other measurement devices or temporary temperature measurement without interrupting the process. It is specially designed for climatization and general application in building automation and heat exchangers.

  • 利点

    • Suitable for high process pressures (no direct contact with the process)

    • Field of application in heavy duty industrial processes

  • アプリケーション

    TST602 RTD thermometer is a general purpose thermometer for surface measurements. It is suitable for application on flat surfaces or pipes and is specially designed for climatization and general application in building automation and heat exchangers.

機能と仕様

戻る

Details

  • 測定原理

    測温抵抗体

  • 特性 / アプリケーション

    メートル法

    ケーブルプローブ

    高プロセス圧力に最適

    表面取付

  • サーモウェル / 保護管

    無し (サーモウェルとの併用無し)

  • インサート / プローブ

    定義されていません

  • 最大浸漬長 要問合わせ

    最大 10,000.00 mm (393.70'')

  • プロセス接続

    表面取付

  • 測定温度レンジ

    PT 100:

    -20 °C ...180 °C

    (-4 °F ...356 °F)

  • 最大プロセス圧力 (静的)

    20 ℃の時:50 MPa (7,252 psi)

  • 精度

    クラス A(IEC 60751基準)

    クラス B(IEC 60751基準)

  • 応答時間

    設定に依存

ドキュメント/マニュアル/ソフトウェア

アクセサリ / スペアパーツ

Nr
Order code
Specification